Duct Size Calculator
Calculate HVAC duct size from airflow (CFM) and design velocity. Get the required duct area, round duct diameter, and a rectangular equivalent for trunks
Duct Size Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: Area = CFM / Velocity | Diameter = โ(4 ร Area / ฯ)
Worked example โ 64 sq in of duct area; use a 10-inch round trunk (actual velocity 400 / 0.545 = 733 ft/min)
Formula
Area = CFM / Velocity | Diameter = โ(4 ร Area / ฯ)
Duct cross-sectional area equals airflow in CFM divided by air velocity in ft/min, giving square feet; multiply by 144 for square inches. The round duct diameter is the square root of 4 times the area divided by pi, rounded up to the next even-inch standard size. Typical residential design velocities are 700-900 ft/min for main trunks and 400-700 ft/min for branch runs to limit noise and friction loss.
Worked Examples
Example 1: Main supply trunk
Problem:A furnace delivers 400 CFM through a main trunk designed at 900 ft/min. What round duct size is needed?
Solution:Area = 400 / 900 = 0.444 sq ft = 0.444 ร 144 = 64.0 sq in Diameter = โ(4 ร 64.0 / ฯ) = 9.0 in Round up to the next even standard size
Result:64 sq in of duct area; use a 10-inch round trunk (actual velocity 400 / 0.545 = 733 ft/min)
Example 2: Bedroom branch run
Problem:A bedroom register needs 120 CFM. Size the branch at a quiet 600 ft/min.
Solution:Area = 120 / 600 = 0.200 sq ft = 28.8 sq in Diameter = โ(4 ร 28.8 / ฯ) = 6.06 in A 6-inch duct is 28.3 sq in, just under the requirement, so round up
Result:Use an 8-inch round branch (50.3 sq in, velocity 120 / 0.349 = 344 ft/min), or a 7-inch duct (38.5 sq in, 449 ft/min) if 7-inch stock is available
Example 3: Converting to a rectangular duct
Problem:The 10-inch round trunk from the first example must fit a 6-inch-deep joist bay. What rectangular size is equivalent?
Solution:Huebscher equivalent: De = 1.30 ร (W ร H)^0.625 / (W + H)^0.25 Try 14 ร 6: 1.30 ร 84^0.625 / 20^0.25 = 1.30 ร 15.96 / 2.115 = 9.8 in Try 16 ร 6: 1.30 ร 96^0.625 / 22^0.25 = 1.30 ร 17.35 / 2.166 = 10.4 in
Result:A 16 ร 6 inch rectangular duct is equivalent to the 10-inch round trunk; note it needs 96 sq in of sheet metal area versus 78.5 sq in for the round duct
Frequently Asked Questions
What velocity should I use?
Main trunks: 700-900 FPM. Branch ducts: 400-700 FPM. Higher velocity = smaller duct but more noise and friction loss.
How do I calculate CFM needed for a room?
The required airflow in cubic feet per minute (CFM) for a room depends on room volume, the required air changes per hour (ACH), and the application. For residential HVAC, a common rule of thumb is 1 CFM per square foot of floor area for cooling. For ventilation, residential codes typically require 0.35 ACH minimum. Commercial spaces per ASHRAE 62.1 typically need 6-10 CFM per person plus 0.06 CFM per square foot of floor area. A more precise method uses Manual J residential load calculations performed by an HVAC engineer.
When should I use round versus rectangular ductwork?
Round ducts are hydraulically more efficient than rectangular ducts of the same cross-sectional area because they have less surface area per unit of cross section, resulting in lower friction losses. Round ducts are also easier to seal, less prone to leaks, and typically cheaper per unit of airflow capacity. Rectangular ducts are preferred when space constraints require a low-profile installation such as in dropped ceilings with limited vertical clearance. High aspect ratio rectangular ducts (width more than 3-4 times height) are significantly less efficient and should be avoided when possible.
What is static pressure and how does it affect duct sizing?
Static pressure in HVAC ducts is the resistance to airflow caused by friction in ductwork, fittings, registers, filters, and coils. A properly designed residential HVAC system typically targets total external static pressure below 0.5 inches of water column. Undersized ducts, sharp bends, long duct runs, and too many fittings all increase static pressure and force the fan to work harder, increasing energy consumption and reducing system lifespan. ASHRAE recommends the Equal Friction Method, which keeps friction loss per unit length constant throughout the system at typically 0.08-0.10 inches of water column per 100 feet of duct.
How do I convert a calculated round size to a rectangular duct?
Size the round duct first from area and velocity, then find rectangular dimensions with the same equivalent diameter using De equal to 1.30 times the product of the sides raised to the 0.625 power, divided by their sum raised to the 0.25 power. Pick standard sheet metal dimensions at or above that result and keep the aspect ratio low, because a flatter duct has more perimeter and more friction for the same area.
How does trunk sizing differ from branch sizing?
A trunk carries the combined airflow of everything downstream, so it is sized for the full CFM at a higher design velocity and is usually reduced in steps as branches peel off. A branch carries only its own register's airflow and is sized at a lower velocity because it discharges near occupants and noise matters more there. Sizing a branch at trunk velocity is a common source of register whistle.
Should I round up or down to the nearest standard duct size?
Round up. Area grows with the square of diameter, so the next size up adds capacity quickly and lowers velocity, friction and noise, while rounding down raises all three at once. The main reasons to round down are physical clearance in a joist bay or a need to keep velocity high enough to carry the throw at the register.
How does flexible duct change the size I should install?
Flexible duct has a corrugated inner liner and a much higher effective roughness than smooth metal, so at the same nominal diameter it loses more pressure. Common practice is to select one nominal size larger than the metal equivalent for any appreciable length, and to pull the duct taut with full support so it is not compressed or sagging, which would erode the extra capacity you just bought.
What is the difference between equal friction and static regain sizing?
Equal friction picks one pressure loss per 100 feet and sizes every duct to it, which is simple and suits residential and small commercial systems. Static regain sizes each downstream section so the pressure recovered as velocity falls at each takeoff offsets the friction in the next run, giving more uniform pressure at every terminal. Regain is normally reserved for long, high velocity commercial trunks.
Why is return duct sizing different from supply?
Return air moves toward the equipment and is usually sized at a lower velocity than supply, because the return path is short, often a central grille or panned joist, and noise transmits straight back to the room. The return still has to move the same mass of air as the supply. Undersized returns starve the blower, raise static pressure and pressurise closed rooms unless transfer grilles or jumper ducts are provided.
References
Background & Theory
History
Reviewed for accuracy by Abdullah, Technical Content Specialist ยท Editorial policy
Related Calculators
๐งฎBreaker Size Calculator
Calculate breaker size with inputs, formulas, and instant results.
๐งฎWire Size Calculator
Calculate wire size with inputs, formulas, and instant results.
๐งฎChicken Coop Size Calculator
Calculate chicken coop size with inputs, formulas, and instant results.
๐งฎDoor Header Size Calculator
Calculate door header size with inputs, formulas, and instant results.
๐งฎDuct Area Calculator
Calculate duct area with inputs, formulas, and instant results.
๐งฎDuct Friction Loss Calculator
Calculate duct friction loss with inputs, formulas, and instant results.
๐งฎExpansion Tank Size Calculator
Calculate expansion tank size with inputs, formulas, and instant results.
๐งฎLintel Header Size Calculator
Calculate lintel header size with inputs, formulas, and instant results.