Wire Size Calculator
Calculate the correct wire gauge for any electrical circuit based on current, voltage, distance, and material.
Wire Size Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: Min R = (V x Drop%) / (I x PhaseFactor x Length) | Ampacity per NEC 310.16
Worked example โ 6 AWG copper | 1.96% voltage drop | 65A ampacity
Formula
Min R = (V x Drop%) / (I x PhaseFactor x Length) | Ampacity per NEC 310.16
Wire size is determined by the larger of two requirements: the NEC ampacity rating (based on current and insulation temperature) and the maximum resistance allowed to keep voltage drop within limits. The maximum allowable resistance per 1,000 feet is calculated from the voltage, allowable drop percentage, current, phase factor (2 for single-phase, 1.732 for three-phase), and distance.
Worked Examples
Example 1: Residential 240V Circuit
Problem:Size copper wire for a 40A, 240V single-phase load at 120 feet from the panel with 3% max voltage drop.
Solution:Ampacity: 8 AWG copper rated 50A at 75C (meets 40A) Voltage drop check for 8 AWG: 2 x 40 x (0.778/1000) x 120 = 7.47V = 3.11% Exceeds 3%, try 6 AWG: 2 x 40 x (0.491/1000) x 120 = 4.71V = 1.96% Use 6 AWG (determined by voltage drop)
Result:6 AWG copper | 1.96% voltage drop | 65A ampacity
Example 2: Commercial 3-Phase Feeder
Problem:Size aluminum wire for 175A, 480V 3-phase feeder at 250 feet with 3% max drop.
Solution:Ampacity: 3/0 AWG aluminum rated 155A (too small), need 4/0 at 180A Voltage drop for 4/0 Al: 1.732 x 175 x (0.100/1000) x 250 = 7.58V = 1.58% 4/0 works for both ampacity and voltage drop.
Result:4/0 AWG aluminum | 1.58% voltage drop | 180A ampacity
Frequently Asked Questions
How do I determine the correct wire size?
Wire size is determined by two independent requirements: ampacity (the maximum current the wire can safely carry without overheating) and voltage drop (keeping the voltage loss within acceptable limits). You must check both and use the larger wire. NEC Table 310.16 provides ampacity ratings for different wire sizes, insulation types, and installation conditions. For voltage drop, the NEC recommends no more than 3% for branch circuits and 5% total. Long runs often require upsizing wire beyond the minimum ampacity requirement to keep voltage drop acceptable.
What is the difference between 60C and 75C ampacity ratings?
The temperature rating refers to the maximum continuous conductor temperature the wire insulation can handle. NEC Table 310.16 lists different ampacity values for 60C (e.g., TW, UF), 75C (e.g., THW, THWN, XHHW), and 90C (e.g., THHN, XHHW-2) insulation types. Higher temperature ratings allow more current because the insulation can withstand more heat. However, the termination temperature rating often limits which column you can use. Most equipment terminals are rated for 75C, so even with 90C wire, you typically must use the 75C ampacity column. For circuits 100A or less, some terminals are only rated for 60C.
When should I use aluminum instead of copper wire?
Aluminum wire is commonly used for service entrance conductors, large feeders (4 AWG and larger), and utility connections because it costs significantly less than copper for the same current capacity. However, aluminum must be sized approximately two AWG sizes larger than copper to carry the same current. Aluminum requires anti-oxidant compound at all connections and terminals specifically rated for aluminum (marked AL or AL/CU). Aluminum is not recommended for branch circuits due to historical connection problems with smaller sizes. For 100A and larger feeders, aluminum offers substantial cost savings with proper installation.
How does conduit fill affect wire sizing?
When multiple current-carrying conductors are installed in the same conduit, their ampacity must be derated per NEC Table 310.15(C)(1). For 4-6 conductors, ampacity is reduced to 80%. For 7-9 conductors, it drops to 70%. For 10-20 conductors, only 50% of the table ampacity can be used. This is because conductors bundled together cannot dissipate heat as effectively as individual conductors in free air. Additionally, the conduit must be sized per NEC Chapter 9 to ensure proper fill percentages, typically 40% maximum for three or more conductors.
Why does the voltage drop formula use a phase factor of 2 for single-phase and 1.732 for three-phase?
Voltage drop depends on the total conductor path the current sees. On a single-phase circuit the current travels out on one conductor and back on the other, so the resistive path is twice the one-way run length, giving a factor of 2. On a balanced three-phase circuit the return current is shared among the phases and the line-to-line drop works out to the square root of 3, about 1.732, times the one-way length. That is why a three-phase feeder can carry the same power over the same distance with a smaller conductor.
Do I use the one-way run length or the total length of wire installed?
Use the one-way distance from the panel to the load, because the phase factor already accounts for the return path. Entering the round-trip length together with the phase factor doubles the drop and pushes the calculation toward a needlessly large conductor. Measure the actual routed path rather than a straight line, since conduit that runs up a wall, across a ceiling and back down can be considerably longer than the floor-plan distance between the two points.
How do ambient temperature and conductor bundling reduce ampacity?
Table ampacities assume a 30 degree Celsius ambient and no more than three current-carrying conductors in a raceway. Hotter surroundings, such as an attic or a rooftop conduit, leave less margin before the insulation reaches its rated temperature, so a correction factor below 1.0 applies. Running more than three current-carrying conductors together traps heat and calls for a further adjustment factor. Both derates multiply the table value, and the derated ampacity, not the table figure, is what must cover the load.
What is a continuous load and how does it change the conductor size?
A continuous load is one expected to run at its maximum current for three hours or more, such as lighting circuits, electric heat or an EV charger. For those, the conductor and the overcurrent device are sized for 125 percent of the continuous current, which is the same thing as loading them to no more than 80 percent of their rating. A 40 amp continuous load therefore needs conductors and a breaker rated for at least 50 amps even though the measured current never exceeds 40.
If I upsize the wire for voltage drop, can I also use a larger breaker?
No. The overcurrent device protects the conductor and the equipment downstream, so its rating is set by the load and the equipment listing, not by whatever conductor happens to be installed. Upsizing conductors for voltage drop is a performance choice and leaves the breaker unchanged. One thing that does change is the equipment grounding conductor, which must be increased in proportion when the ungrounded conductors are enlarged, so that the fault-clearing path keeps pace.
How does AWG numbering relate to actual conductor area?
American Wire Gauge runs backwards: the number falls as the conductor gets larger, so 10 AWG is bigger than 14 AWG. The scale is geometric, and cross-sectional area roughly doubles for every three gauge steps, which is why going from 12 AWG to 6 AWG about quadruples the copper. Above 4/0 the gauge scale stops and conductors are specified directly in thousands of circular mils, written as kcmil. Resistance per unit length falls in the same proportion as area rises, which is what drives the voltage drop result.
References
Background & Theory
History
Reviewed for accuracy by Abdullah, Technical Content Specialist ยท Editorial policy
Related Calculators
๐งฎBreaker Size Calculator
Calculate breaker size with inputs, formulas, and instant results.
๐งฎChicken Coop Size Calculator
Calculate chicken coop size with inputs, formulas, and instant results.
๐งฎDoor Header Size Calculator
Calculate door header size with inputs, formulas, and instant results.
๐งฎExpansion Tank Size Calculator
Calculate expansion tank size with inputs, formulas, and instant results.
๐งฎLintel Header Size Calculator
Calculate lintel header size with inputs, formulas, and instant results.
๐งฎDuct Size Calculator
Calculate duct size with inputs, formulas, and instant results.
๐งฎPipe Size Calculator
Calculate pipe size with inputs, formulas, and instant results.
๐งฎFooting Size Calculator
Calculate required footing size based on column load and soil bearing capacity.