Wire Size Calculator
Calculate wire size accurately for your build. Get material quantities, waste allowances, and project cost breakdowns. Free to use with no signup required.
Reviewed for accuracy by Abdullah, Technical Content Specialist
Wire Size Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: Min R = (V x Drop%) / (I x PhaseFactor x Length) | Ampacity per NEC 310.16
Worked example โ 6 AWG copper | 1.96% voltage drop | 65A ampacity
Formula
Min R = (V x Drop%) / (I x PhaseFactor x Length) | Ampacity per NEC 310.16
Wire size is determined by the larger of two requirements: the NEC ampacity rating (based on current and insulation temperature) and the maximum resistance allowed to keep voltage drop within limits. The maximum allowable resistance per 1,000 feet is calculated from the voltage, allowable drop percentage, current, phase factor (2 for single-phase, 1.732 for three-phase), and distance.
Worked Examples
Example 1: Residential 240V Circuit
Problem:Size copper wire for a 40A, 240V single-phase load at 120 feet from the panel with 3% max voltage drop.
Solution:Ampacity: 8 AWG copper rated 50A at 75C (meets 40A) Voltage drop check for 8 AWG: 2 x 40 x (0.778/1000) x 120 = 7.47V = 3.11% Exceeds 3%, try 6 AWG: 2 x 40 x (0.491/1000) x 120 = 4.71V = 1.96% Use 6 AWG (determined by voltage drop)
Result:6 AWG copper | 1.96% voltage drop | 65A ampacity
Example 2: Commercial 3-Phase Feeder
Problem:Size aluminum wire for 175A, 480V 3-phase feeder at 250 feet with 3% max drop.
Solution:Ampacity: 3/0 AWG aluminum rated 155A (too small), need 4/0 at 180A Voltage drop for 4/0 Al: 1.732 x 175 x (0.100/1000) x 250 = 7.58V = 1.58% 4/0 works for both ampacity and voltage drop.
Result:4/0 AWG aluminum | 1.58% voltage drop | 180A ampacity
Frequently Asked Questions
How do I determine the correct wire size?
Wire size is determined by two independent requirements: ampacity (the maximum current the wire can safely carry without overheating) and voltage drop (keeping the voltage loss within acceptable limits). You must check both and use the larger wire. NEC Table 310.16 provides ampacity ratings for different wire sizes, insulation types, and installation conditions. For voltage drop, the NEC recommends no more than 3% for branch circuits and 5% total. Long runs often require upsizing wire beyond the minimum ampacity requirement to keep voltage drop acceptable.
What is the difference between 60C and 75C ampacity ratings?
The temperature rating refers to the maximum continuous conductor temperature the wire insulation can handle. NEC Table 310.16 lists different ampacity values for 60C (e.g., TW, UF), 75C (e.g., THW, THWN, XHHW), and 90C (e.g., THHN, XHHW-2) insulation types. Higher temperature ratings allow more current because the insulation can withstand more heat. However, the termination temperature rating often limits which column you can use. Most equipment terminals are rated for 75C, so even with 90C wire, you typically must use the 75C ampacity column. For circuits 100A or less, some terminals are only rated for 60C.
When should I use aluminum instead of copper wire?
Aluminum wire is commonly used for service entrance conductors, large feeders (4 AWG and larger), and utility connections because it costs significantly less than copper for the same current capacity. However, aluminum must be sized approximately two AWG sizes larger than copper to carry the same current. Aluminum requires anti-oxidant compound at all connections and terminals specifically rated for aluminum (marked AL or AL/CU). Aluminum is not recommended for branch circuits due to historical connection problems with smaller sizes. For 100A and larger feeders, aluminum offers substantial cost savings with proper installation.
How does conduit fill affect wire sizing?
When multiple current-carrying conductors are installed in the same conduit, their ampacity must be derated per NEC Table 310.15(C)(1). For 4-6 conductors, ampacity is reduced to 80%. For 7-9 conductors, it drops to 70%. For 10-20 conductors, only 50% of the table ampacity can be used. This is because conductors bundled together cannot dissipate heat as effectively as individual conductors in free air. Additionally, the conduit must be sized per NEC Chapter 9 to ensure proper fill percentages, typically 40% maximum for three or more conductors.
How do I size an HVAC system for a building?
HVAC sizing uses Manual J calculations considering square footage, insulation, window area, climate zone, and occupancy. A rough estimate is 1 ton of cooling per 400-600 square feet. Oversized systems short-cycle and waste energy; undersized systems cannot maintain comfort.
References
Background & Theory
History
Reviewed for accuracy by Abdullah, Technical Content Specialist ยท Editorial policy
Related Calculators
๐งฎBreaker Size Calculator
Calculate breaker size with inputs, formulas, and instant results.
๐งฎChicken Coop Size Calculator
Calculate chicken coop size with inputs, formulas, and instant results.
๐งฎDoor Header Size Calculator
Calculate door header size with inputs, formulas, and instant results.
๐งฎExpansion Tank Size Calculator
Calculate expansion tank size with inputs, formulas, and instant results.
๐งฎLintel Header Size Calculator
Calculate lintel header size with inputs, formulas, and instant results.
๐งฎDuct Size Calculator
Calculate duct size with inputs, formulas, and instant results.
๐งฎPipe Size Calculator
Calculate pipe size with inputs, formulas, and instant results.
๐งฎFooting Size Calculator
Calculate required footing size based on column load and soil bearing capacity.