Psychrometric Calculator
Calculate psychrometric properties of moist air including humidity ratio, dew point, wet bulb temperature, enthalpy, and specific volume from dry bulb
Psychrometric Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: W = 0.62198 * Pw / (P - Pw) where Pw = (RH/100) * Pws
Worked example โ W = 9.30 g/kg | Dew Point = 12.9 C | Enthalpy = 47.8 kJ/kg
Formula
W = 0.62198 * Pw / (P - Pw) where Pw = (RH/100) * Pws
Where W is humidity ratio (kg/kg), Pw is partial vapor pressure, Pws is saturation vapor pressure from the Magnus formula, P is atmospheric pressure, and RH is relative humidity percentage.
Worked Examples
Example 1: Office HVAC Design Conditions
Problem:Find all psychrometric properties for indoor design conditions: dry bulb 24 C, 50% RH, at standard atmospheric pressure 101.325 kPa.
Solution:Saturation pressure: Pws = 0.61078 * exp(17.27*24/(24+237.3)) = 2.984 kPa Vapor pressure: Pw = 0.50 * 2.984 = 1.492 kPa Humidity ratio: W = 0.62198 * 1.492 / (101.325 - 1.492) = 0.00930 kg/kg = 9.30 g/kg Dew point: Td = 237.3 * ln(1.492/0.61078) / (17.27 - ln(1.492/0.61078)) = 12.9 C Enthalpy: h = 1.006*24 + 0.00930*(2501 + 1.86*24) = 47.8 kJ/kg
Result:W = 9.30 g/kg | Dew Point = 12.9 C | Enthalpy = 47.8 kJ/kg
Example 2: Hot Humid Summer Conditions
Problem:Determine psychrometric properties for outdoor summer air at 35 C, 80% RH, 101.325 kPa.
Solution:Saturation pressure: Pws = 0.61078 * exp(17.27*35/(35+237.3)) = 5.624 kPa Vapor pressure: Pw = 0.80 * 5.624 = 4.499 kPa Humidity ratio: W = 0.62198 * 4.499 / (101.325 - 4.499) = 0.02889 kg/kg = 28.89 g/kg Dew point: Td = 237.3 * ln(4.499/0.61078) / (17.27 - ln(4.499/0.61078)) = 31.0 C Enthalpy: h = 1.006*35 + 0.02889*(2501 + 1.86*35) = 109.4 kJ/kg
Result:W = 28.89 g/kg | Dew Point = 31.0 C | Enthalpy = 109.4 kJ/kg
Frequently Asked Questions
What is psychrometrics and why is it important in HVAC engineering?
Psychrometrics is the study of the thermodynamic properties of moist air, which is a mixture of dry air and water vapor. It is fundamental to HVAC (Heating, Ventilation, and Air Conditioning) engineering because every aspect of indoor climate control depends on understanding how air and moisture interact. Engineers use psychrometric data to design air conditioning systems, calculate cooling and heating loads, control humidity in buildings, and ensure occupant comfort. Without accurate psychrometric calculations, HVAC systems would be improperly sized, leading to energy waste, poor indoor air quality, mold growth, or uncomfortable conditions. The psychrometric chart, which graphically represents these relationships, is one of the most essential tools in mechanical engineering practice.
What is the difference between dry bulb, wet bulb, and dew point temperatures?
These three temperatures describe different aspects of moist air. Dry bulb temperature is the ordinary air temperature measured by a standard thermometer shielded from radiation and moisture. Wet bulb temperature is measured by wrapping a thermometer bulb with a wet wick and allowing air to flow over it; evaporation cools the bulb, and the reading depends on how much moisture the air can still absorb. Dew point temperature is the temperature at which the air becomes fully saturated and water vapor begins to condense into liquid droplets. The dew point is always less than or equal to the dry bulb temperature, and the wet bulb falls between the two. When all three temperatures are equal, the air is at 100% relative humidity and fully saturated.
How is humidity ratio different from relative humidity?
Humidity ratio (also called mixing ratio or specific humidity) is the actual mass of water vapor per unit mass of dry air, typically expressed in grams per kilogram. It is an absolute measure that does not change with temperature alone. Relative humidity, on the other hand, is the ratio of the current vapor pressure to the saturation vapor pressure at that temperature, expressed as a percentage. Relative humidity changes with temperature even if the actual moisture content stays the same. For example, air at 20 degrees Celsius and 50% relative humidity has the same moisture content as air at about 9 degrees Celsius and 100% relative humidity. HVAC engineers often prefer humidity ratio because it directly indicates the moisture load that equipment must handle.
What is enthalpy in psychrometric calculations and how is it used?
Enthalpy in psychrometric calculations represents the total heat content of moist air per kilogram of dry air, measured in kilojoules per kilogram. It includes both the sensible heat (related to temperature) and the latent heat (related to moisture content). The formula combines the dry air component (approximately 1.006 times the dry bulb temperature) with the water vapor component (humidity ratio multiplied by the sum of the latent heat of vaporization at zero degrees and the specific heat of steam times the temperature). HVAC engineers use enthalpy to calculate cooling and heating loads, design air handling units, and determine the energy required for various air conditioning processes such as heating, cooling, humidification, and dehumidification.
How does atmospheric pressure affect psychrometric calculations?
Atmospheric pressure significantly affects all psychrometric properties because it changes the density of air and the behavior of water vapor within it. At higher altitudes where pressure is lower, the saturation vapor pressure remains the same (it depends only on temperature), but the humidity ratio for a given relative humidity increases because there is less dry air per unit volume. This means air conditioning equipment at high altitudes must handle more moisture per unit mass of dry air. Standard psychrometric charts are drawn for sea-level pressure of 101.325 kPa, but engineers working at different altitudes must use corrected charts or calculations. A 1000-meter increase in elevation reduces atmospheric pressure by roughly 11%, which noticeably changes enthalpy and humidity ratio values.
What is the sensible heat ratio, and how does it split a cooling load?
Sensible load is the part that changes dry bulb temperature; latent load is the part that removes water vapour and appears only as a fall in humidity ratio. Sensible heat ratio is the sensible portion divided by the total, and total load follows directly from the enthalpy change: mass flow of dry air multiplied by the difference in enthalpy. A densely occupied room or one with a high outdoor air rate has a low SHR and needs a coil that dehumidifies hard; a sunlit space with little moisture gain has a high SHR.
What do apparatus dew point and coil bypass factor describe?
Air leaving a cooling coil is really a mixture: some of it touches the fins and leaves close to saturated at the surface condition, and some slips through untouched. Extending the straight line from entering to leaving condition until it meets the saturation curve gives the apparatus dew point, the effective coil surface temperature. Bypass factor is the fraction that escapes contact; it falls as rows and fin density increase and rises with face velocity. Together they decide how low a leaving humidity ratio a given coil can actually reach.
Why is wet bulb temperature the floor for evaporative cooling?
In an adiabatic saturation process the heat needed to evaporate water comes from the air itself, so dry bulb falls while humidity ratio rises and enthalpy stays almost unchanged. The process therefore tracks a line of nearly constant wet bulb, and the lowest dry bulb reachable is the entering wet bulb temperature, attained only at complete saturation. Real media reach some fraction of that, quoted as saturation effectiveness. It also explains why evaporative cooling performs well in dry climates and poorly in humid ones.
What does the dew point tell me about condensation risk on ducts and windows?
Condensation appears wherever a surface sits at or below the dew point of the air touching it, since that air can no longer hold its vapour. Take the dew point computed from room dry bulb and relative humidity, then compare it with the coldest surface temperature you expect: single glazing on a winter night, an uninsulated chilled water pipe, or a supply duct crossing a humid ceiling void. Insulation thickness and vapour barriers are selected precisely to keep outer surface temperature above that dew point.
Why convert a fan's volumetric airflow into a dry air mass flow?
Psychrometric properties such as humidity ratio and enthalpy are quoted per kilogram of dry air, while fans, diffusers and dampers are rated in cubic metres per second. Specific volume bridges the two: divide volumetric flow by the specific volume shown here to obtain kilograms of dry air per second, which is what load equations need. Specific volume grows with temperature and with altitude, so applying a sea level figure at a hot or high site overstates the air mass actually delivered and leaves installed capacity short of design.
References
Background & Theory
History
Reviewed for accuracy by Daniel Agrici, Founder & Lead Developer ยท Editorial policy
Related Calculators
๐งฎCantilever Retaining Wall Calculator
Calculate cantilever retaining wall with inputs, formulas, and instant results.
๐งฎOpen Channel Manning Calculator
Calculate open channel manning with inputs, formulas, and instant results.
๐งฎPipe Flow Darcy Weisbach Calculator
Calculate pipe flow darcy weisbach with inputs, formulas, and instant results.
๐งฎRoad Superelevation Calculator
Calculate road superelevation with inputs, formulas, and instant results.
๐งฎRlccircuit Impedance Calculator
Calculate rlccircuit impedance with inputs, formulas, and instant results.
๐งฎThree Phase Power Calculator
Calculate three phase power with inputs, formulas, and instant results.
๐งฎTransformer Turns Ratio Calculator
Calculate transformer turns ratio with inputs, formulas, and instant results.