Sensible Heat Load Calculator
Calculate sensible heat load in BTU/h and tons of cooling from airflow, temperature difference, and altitude.
Sensible Heat Load Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: Q = 1.08 x CFM x Delta-T (at sea level)
Worked example โ Sensible heat load of 21,600 BTU/h or 1.80 tons of cooling
Formula
Q = 1.08 x CFM x Delta-T (at sea level)
Sensible heat (Q) in BTU per hour equals 1.08 multiplied by the air volume flow rate in CFM and the temperature difference in degrees Fahrenheit. The constant 1.08 is derived from the specific heat of air (0.24 BTU/lb/F), standard air density (0.075 lb/ft3), and 60 minutes per hour. An altitude correction factor adjusts for lower air density at elevation.
Worked Examples
Example 1: Office Building Cooling Load
Problem:Calculate the sensible cooling load for 1000 CFM of air cooled from 95 degrees F to 75 degrees F at sea level.
Solution:Delta-T = 95 - 75 = 20 degrees F Q = 1.08 x 1000 x 20 = 21,600 BTU/h Tons = 21,600 / 12,000 = 1.80 tons With 10% safety = 23,760 BTU/h = 1.98 tons
Result:Sensible heat load of 21,600 BTU/h or 1.80 tons of cooling
Example 2: High Altitude Warehouse Heating
Problem:Calculate sensible heat to warm 5000 CFM from 35 degrees F to 70 degrees F at 5000 feet elevation.
Solution:Delta-T = 70 - 35 = 35 degrees F Density ratio at 5000 ft = 0.832 Q = 0.832 x 1.08 x 5000 x 35 = 157,248 BTU/h With 10% safety = 172,973 BTU/h
Result:Sensible heat load of 157,248 BTU/h (altitude-corrected)
Frequently Asked Questions
What is sensible heat load in HVAC?
Sensible heat load is the amount of thermal energy that must be added or removed from air to change its temperature without changing its moisture content. It is measured in BTU per hour and is the primary factor in sizing air conditioning and heating equipment. Sensible heat differs from latent heat, which involves moisture changes. In a typical cooling application, sensible heat accounts for 60 to 80 percent of the total cooling load.
How is the sensible heat formula derived?
The standard formula Q = 1.08 x CFM x Delta-T combines several constants. The specific heat of air is 0.24 BTU per pound per degree F, standard air density is 0.075 lb per cubic foot, and 60 minutes per hour converts CFM to cubic feet per hour. Multiplying these together gives 0.24 x 0.075 x 60 = 1.08. This constant is only accurate at sea-level standard conditions and must be adjusted for higher altitudes where air density decreases.
Why does altitude affect sensible heat calculations?
At higher altitudes, atmospheric pressure decreases, which reduces air density. Since the sensible heat formula depends on the mass flow rate of air (not just volume), lower density means less mass per cubic foot and therefore less heat transfer per CFM. At 5000 feet elevation, air density is about 83 percent of sea-level density, so the 1.08 factor drops to approximately 0.90. Failing to correct for altitude leads to undersized equipment.
What safety factor should I apply to sensible heat calculations?
Most HVAC engineers apply a 10 to 15 percent safety factor to calculated sensible heat loads to account for uncertainties in occupancy, equipment heat gains, solar gain variations, and aging of the system. Over-sizing beyond 20 percent should be avoided because it causes short cycling in cooling equipment, which reduces dehumidification performance and wastes energy. Variable speed systems can tolerate slightly higher safety factors without the short cycling penalty.
How do I convert a sensible heat load in BTU per hour into tons of cooling?
One ton of refrigeration is 12,000 BTU per hour, a figure that comes from the heat needed to melt one short ton of ice in 24 hours. Divide the calculated load by 12,000 to express it in tons. Remember that equipment is rated on total capacity, which includes the latent portion, so a sensible load of 36,000 BTU per hour does not by itself mean a three ton unit is correctly sized.
What is the sensible heat ratio and why does it matter for equipment selection?
The sensible heat ratio, or SHR, is sensible load divided by total load. A dry climate office runs a high SHR because very little of its load is moisture, while a humid or densely occupied space runs lower because more of the load is moisture removal. Equipment has its own rated SHR at given conditions. Matching a high-SHR machine to a low-SHR space leaves the room cool but clammy, because the coil satisfies the thermostat before it removes enough moisture.
How do I find the airflow needed to carry a given sensible load?
Rearrange the formula to CFM equals Q divided by 1.08 times delta-T. A 24,000 BTU per hour sensible load carried at a 20 degree F supply-to-room temperature difference needs 24,000 divided by 21.6, about 1,111 CFM. Choosing a larger delta-T lowers the airflow and shrinks the ductwork, but supply air that is too cold risks condensation on diffusers and draft complaints in the occupied zone.
What formulas cover the latent and total heat that Sensible Heat Load Calculator does not?
Latent heat, the moisture portion, uses Q equals 0.68 times CFM times the humidity ratio difference in grains of moisture per pound of dry air. Total heat uses Q equals 4.5 times CFM times the enthalpy difference in BTU per pound. All three constants share the same derivation from air density and the 60 minute conversion, so each of them requires the same altitude density correction as the 1.08 factor.
What is the difference between the room sensible load and the coil sensible load?
Room sensible load is the heat that must be removed from the occupied space itself. Coil sensible load additionally includes duct heat gain, air leakage from ductwork outside the conditioned envelope, fan motor heat added to the airstream, and any outdoor air brought across the coil. The coil load is therefore always the larger number, and it is the one used to select equipment while the room load sets the supply airflow.
Why is the temperature difference measured dry bulb rather than wet bulb?
Sensible heat is by definition the energy associated with a change in temperature at constant moisture content, and dry bulb temperature is the direct measure of that. Wet bulb temperature responds to both temperature and humidity, so it tracks total enthalpy rather than sensible heat alone. Using a wet bulb difference in the 1.08 formula would mix latent effects into a sensible calculation and give a meaningless result.
References
Background & Theory
History
Reviewed for accuracy by Abdullah, Technical Content Specialist ยท Editorial policy
Related Calculators
๐งฎLatent Heat Load Calculator
Calculate latent heat load with inputs, formulas, and instant results.
๐งฎOccupant Load Calculator
Calculate occupant load with inputs, formulas, and instant results.
๐งฎBridge Deck Load Calculator
Calculate bridge deck load with inputs, formulas, and instant results.
๐งฎCircuit Load Calculator
Calculate circuit load with inputs, formulas, and instant results.
๐งฎNecresidential Load Calculator
Calculate necresidential load with inputs, formulas, and instant results.
๐งฎTransformer Load Calculator
Calculate transformer load with inputs, formulas, and instant results.
๐งฎCooling Load Calculator
Calculate cooling load with inputs, formulas, and instant results.
๐งฎHeating Load Calculator
Calculate heating load with inputs, formulas, and instant results.