Short Circuit Voltage Drop Calculator
Calculate voltage drop and short circuit current for electrical circuits. Determine if your wire size meets NEC recommendations for single-phase.
Short Circuit Voltage Drop Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: VD (1-phase) = 2 x I x R x L | VD (3-phase) = 1.732 x I x R x L
Worked example โ 12 AWG: 9.50V (7.92%) - Too high | 10 AWG: 5.95V (4.96%)
Formula
VD (1-phase) = 2 x I x R x L | VD (3-phase) = 1.732 x I x R x L
Voltage drop equals the current (amps) times the conductor resistance per unit length (ohms/ft) times the one-way conductor length (feet). For single-phase, multiply by 2 for the round-trip path. For three-phase, multiply by 1.732 (square root of 3). Short circuit current at the end of the run is estimated as the source voltage divided by the total circuit resistance.
Worked Examples
Example 1: 120V Branch Circuit
Problem:A 120V, single-phase circuit supplies 16A through 150 feet of 12 AWG copper wire. Calculate voltage drop.
Solution:Resistance: 1.98 ohms/1000ft Voltage drop: 2 x 16 x (1.98/1000) x 150 = 9.50V Percent: 9.50 / 120 x 100 = 7.92% This exceeds the 3% NEC recommendation. Upgrade to 10 AWG: 2 x 16 x (1.24/1000) x 150 = 5.95V (4.96%)
Result:12 AWG: 9.50V (7.92%) - Too high | 10 AWG: 5.95V (4.96%)
Example 2: 480V Three-Phase Feeder
Problem:A 480V, 3-phase feeder supplies 200A through 300 feet of 3/0 AWG copper.
Solution:Resistance: 0.0766 ohms/1000ft Voltage drop: 1.732 x 200 x (0.0766/1000) x 300 = 7.96V Percent: 7.96 / 480 x 100 = 1.66% Well within 3% limit.
Result:7.96V drop (1.66%) - Compliant with NEC 3% recommendation
Frequently Asked Questions
What is acceptable voltage drop per NEC?
The NEC recommends (but does not mandate as a hard requirement) a maximum voltage drop of 3% for branch circuits and 5% total for the combination of feeder and branch circuit. NEC Article 210.19(A) Informational Note No. 4 and Article 215.2(A) Informational Note No. 2 provide this guidance. While not a code violation to exceed these values, excessive voltage drop causes motors to overheat, lighting to dim, and electronic equipment to malfunction. Many engineers design for 2% on feeders and 3% on branch circuits to stay well within limits.
How does wire size affect voltage drop?
Larger wire sizes have lower resistance per foot, which directly reduces voltage drop. For example, upgrading from 10 AWG copper (1.24 ohms/1000ft) to 8 AWG copper (0.778 ohms/1000ft) reduces resistance by 37%. The relationship is that doubling the wire cross-sectional area (going up approximately 3 AWG sizes) roughly halves the resistance and voltage drop. For long runs, it is often more economical to upsize the wire by one or two sizes rather than deal with the ongoing energy losses and performance issues from excessive voltage drop.
What is the difference between copper and aluminum conductors?
Copper has about 61% lower resistance than aluminum for the same wire gauge, meaning copper wires carry more current with less voltage drop. However, aluminum is lighter and less expensive per foot. To carry the same current, aluminum wire must be approximately two AWG sizes larger than copper (for example, 2 AWG aluminum replaces 4 AWG copper). Aluminum requires special connectors rated for aluminum use and proper anti-oxidant compound to prevent connection failures. Copper is preferred for branch circuits and smaller feeders, while aluminum is commonly used for large feeders and service entrance conductors.
How do I calculate voltage drop for three-phase circuits?
Three-phase voltage drop uses a different formula than single-phase. For single-phase: VD = 2 x I x R x L, where the factor of 2 accounts for the current traveling through both the hot and neutral conductors. For three-phase: VD = 1.732 x I x R x L, where 1.732 (square root of 3) replaces the factor of 2 because of the 120-degree phase relationship between the three conductors. This means three-phase circuits have approximately 13% less voltage drop than single-phase circuits for the same wire size, current, and distance, making them more efficient for long runs.
When is DC resistance not enough, and impedance needed instead?
This calculation uses conductor DC resistance only. Alternating current also sees reactance from the magnetic field around the conductors, plus skin and proximity effects that push current toward the conductor surface. Those additions are minor for small branch circuits but become significant above roughly 1/0, in steel raceway, and at low power factor. For large feeders, use the effective impedance tables that account for conductor spacing and raceway material.
How does conductor temperature change the voltage drop?
Metal resistance rises with temperature: copper increases roughly 0.4 percent per degree Celsius. Published resistance values are tabulated at a stated temperature, so a conductor running hot under near-full load has meaningfully higher resistance and therefore more drop than the table value implies. Since voltage drop is usually checked at full load, when the conductor is hottest, using an ambient-temperature resistance value understates the worst case.
Which voltage is percent voltage drop measured against?
Percent drop is the calculated drop divided by the nominal system voltage at the source, times 100. For single-phase circuits the reference is whatever voltage that circuit actually operates at: a line-to-neutral 120 or 277 volt circuit is compared against that value, while a 240 or 208 volt line-to-line single-phase circuit uses the same VD = 2 x I x R x L formula but is compared against the line-to-line voltage. For three-phase circuits the 1.732 formula produces a line-to-line drop, so it must be divided by the line-to-line voltage such as 208 or 480. Mixing line-to-neutral and line-to-line values is a frequent source of results wrong by a factor of 1.732.
Why is the short-circuit figure here only an approximation?
Estimating fault current as source voltage divided by conductor resistance ignores the impedance of the supply transformer and the utility system upstream, which usually dominates the total near the service. It also ignores conductor reactance and motor contribution. The result is useful as an order-of-magnitude check on how fault current decays along a long run, but interrupting ratings must be selected from a proper study using transformer impedance data.
What is the difference between sizing a conductor for ampacity and sizing it for voltage drop?
Ampacity sizing is a code requirement about heat: the conductor must carry the load current without exceeding its insulation temperature rating, after correction for ambient temperature and for the number of current-carrying conductors bundled together. Voltage drop is a performance concern about length. A short run is almost always governed by ampacity, and a long run by voltage drop, but both checks must be satisfied and the larger size governs.
How do I pick a conductor size to meet a target voltage drop?
Rearrange for the resistance you can afford. On a single-phase run, the maximum allowable resistance per foot equals the target drop divided by 2 times current times one-way length. For 20 amps over 100 feet at a 3.6 volt target, that is 3.6 divided by 4,000, or 0.0009 ohms per foot, which is 0.9 ohms per 1,000 feet. Then choose the first standard size whose tabulated resistance falls below that figure.
References
Background & Theory
History
Reviewed for accuracy by Abdullah, Technical Content Specialist ยท Editorial policy
Related Calculators
๐งฎCurrent Capacity Calculator
Calculate current capacity with inputs, formulas, and instant results.
๐งฎFault Current Available Calculator
Calculate fault current available with inputs, formulas, and instant results.
๐งฎPower Factor Calculator
Calculate power factor with inputs, formulas, and instant results.
๐งฎPump Power Calculator
Calculate pump power with inputs, formulas, and instant results.
๐งฎOutdoor Lighting Calculator
Calculate low-voltage outdoor lighting transformer size from total fixture wattage.
๐งฎCircuit Load Calculator
Calculate circuit load with inputs, formulas, and instant results.
๐งฎCeiling Fan Wiring Calculator
Determine wire gauge and circuit requirements for ceiling fan installation.
๐งฎConstruction Equipment CO2 Calculator
Calculate carbon footprint construction equipment with inputs, formulas, and instant results.