Current Capacity Calculator
Free Current capacity Calculator for electrical engineering projects. Enter dimensions to get material lists and cost estimates.
Current Capacity Calculator
Calculator
Adjust values & calculateEnter your values below. Every result is computed in your browser โ no data is sent to any server.
Formula: Derated Ampacity = Base Ampacity x Temp Factor x Fill Factor
Worked example โ 21.8A derated, 17.5A continuous capacity
Formula
Derated Ampacity = Base Ampacity x Temp Factor x Fill Factor
Start with the base ampacity from NEC Table 310.16 for the wire gauge and insulation temperature rating. Multiply by the ambient temperature correction factor from Table 310.15(B)(1). Then multiply by the conduit fill adjustment factor from 310.15(C)(1) based on the number of current-carrying conductors. The result is the maximum safe current the wire can carry continuously.
Worked Examples
Example 1: Standard Circuit at 75C
Problem:Find the derated ampacity of 10 AWG THHN wire with 6 conductors in conduit at 95F ambient.
Solution:Base ampacity for 10 AWG = 30A (NEC 240.4(D) caps overcurrent protection for 10 AWG at 30A, so this calculator starts there) Temp correction at 35C / 95F = 0.91 Fill adjustment for 4 to 6 current-carrying conductors = 0.80 Derated = 30 x 0.91 x 0.80 = 21.8A Continuous load limit (80%) = 17.5A
Result:21.8A derated, 17.5A continuous capacity
Example 2: Heavy Feeder Run
Problem:Find capacity of 4/0 AWG at 75C with 3 conductors at normal temperature.
Solution:Base ampacity = 230A Temp correction (30C) = 1.00 Fill derating (3 conductors) = 1.00 Derated = 230 x 1.00 x 1.00 = 230A Continuous = 184A
Result:230A full capacity, 184A continuous
Frequently Asked Questions
What is the current capacity (ampacity) of copper wire?
Current capacity, or ampacity, is the maximum amount of electrical current a conductor can carry continuously without exceeding its insulation temperature rating. Per NEC Table 310.16, common copper wire ampacities at 75 degrees C are: 14 AWG at 20 amps, 12 AWG at 25 amps, 10 AWG at 35 amps, 8 AWG at 50 amps, 6 AWG at 65 amps, 4 AWG at 85 amps, 2 AWG at 115 amps, and 1/0 at 150 amps. NEC 240.4(D) separately caps overcurrent protection for the three smallest of these at 15, 20 and 30 amps respectively, and Current Capacity Calculator starts from those capped values because they are what actually limits the breaker. All table ratings assume no more than 3 current-carrying conductors in a raceway and an ambient temperature of 86 degrees F (30 degrees C); higher temperatures or more conductors require derating.
How does ambient temperature affect wire ampacity?
Higher ambient temperatures reduce wire ampacity because the conductor starts closer to its maximum insulation temperature and has less room for heat generated by current flow. NEC Table 310.15(B)(1) provides correction factors for ambient temperatures above 86 degrees F (30 degrees C). At 104 degrees F (40 degrees C), the correction factor for 75-degree C insulation is 0.82, reducing a 20-amp rating to 16.4 amps. At 122 degrees F (50 degrees C), the factor drops to 0.58. Wires in hot attics, near heat sources, or in direct sunlight must be derated accordingly. This is one of the most commonly overlooked derating requirements.
What is conduit fill derating for current capacity?
When multiple current-carrying conductors share a conduit, each conductor generates heat that affects the others, requiring ampacity reduction per NEC 310.15(C)(1). For 4 to 6 conductors, ampacity is reduced to 80 percent of the table value. For 7 to 9 conductors, it drops to 70 percent. For 10 to 20 conductors, the factor is 50 percent. For 21 to 30 conductors, it is 45 percent. Neutral conductors carrying only unbalanced current are typically not counted, nor are equipment grounding conductors. This derating stacks with temperature correction, so a wire in a hot conduit with many conductors can have significantly reduced capacity.
What is the difference between 60C, 75C, and 90C rated wire?
The temperature rating (60C, 75C, 90C) indicates the maximum continuous operating temperature the wire insulation can withstand. Common 60C insulations include TW and UF. The 75C rating covers THWN, XHHW, and USE, which are the most common for residential and commercial wiring. The 90C rating includes THHN, THWN-2, and XHHW-2. Higher temperature ratings allow greater ampacity because the wire can safely run hotter. However, NEC 110.14(C) limits the ampacity you can use based on the equipment terminal ratings, which are typically 60C or 75C. The 90C rating is mainly useful when applying derating factors.
What is the 125 percent continuous load rule?
A continuous load is one expected to run at its maximum current for three hours or more, such as lighting or an EV charger. Branch circuit conductors and the overcurrent device must be sized for at least 125 percent of the continuous portion of the load plus 100 percent of the non-continuous portion. This is a separate check from ambient and fill derating: the conductor must satisfy both the 125 percent sizing rule and the adjusted ampacity, and whichever is more demanding governs.
When does voltage drop govern instead of ampacity?
Ampacity is a heat and safety limit; voltage drop is a performance limit that grows with circuit length because it depends on resistance times current, and resistance is proportional to conductor length. On a long run a conductor can be perfectly safe thermally while delivering too little voltage for motors to start or lighting drivers to hold output. The NEC treats voltage drop in informational notes recommending roughly three percent on a branch circuit and five percent overall, so designers upsize beyond the ampacity requirement.
Why is aluminium sized larger than copper for the same current?
Aluminium has roughly 61 percent of copper's conductivity, so an aluminium conductor needs greater cross-sectional area to carry the same current at the same temperature rise, generally about two AWG sizes larger. Modern AA-8000 series alloys have addressed the creep and cold-flow problems of older alloys, but terminations still require devices listed for aluminium, correct torque, and an antioxidant compound where specified. Aluminium's advantage is cost and weight on large feeders and service entrances.
What is the difference between the conductor's ampacity and the breaker rating?
Ampacity is the conductor's own thermal limit; the overcurrent device exists to protect that conductor. Normally the device rating must not exceed the conductor ampacity, but where the adjusted ampacity does not correspond to a standard breaker size, the next standard size up is permitted for many circuits at 800 amps or less, with exceptions such as circuits supplying receptacles. Terminal temperature limits under 110.14(C) also cap the ampacity you may use regardless of the insulation rating.
Do derating factors multiply, and in what order?
Yes, the ambient temperature correction factor and the conductor count adjustment factor are both applied to the same base ampacity as a product, not chosen by whichever is worse. A conductor whose table ampacity before derating is 30 amps, in a hot location with a 0.82 correction and in a raceway with six current-carrying conductors giving a 0.8 adjustment, has 30 times 0.82 times 0.8, or about 19.7 amps. Multiplication is commutative, so order does not matter.
Why are conductors on a rooftop treated as hotter?
Raceways exposed to direct sunlight above a roof surface heat well beyond shade ambient, because the conduit absorbs solar radiation and the roof membrane below re-radiates. The conductors inside therefore start closer to their insulation limit and lose usable ampacity. The NEC has addressed this with a rooftop temperature adder whose value has changed across code cycles, so check the edition your jurisdiction has adopted. Mounting the raceway clear of the roof to allow airflow beneath reduces the effect.
References
Background & Theory
History
Reviewed for accuracy by Abdullah, Technical Content Specialist ยท Editorial policy
Related Calculators
๐งฎFault Current Available Calculator
Calculate fault current available with inputs, formulas, and instant results.
๐งฎPower Factor Calculator
Calculate power factor with inputs, formulas, and instant results.
๐งฎShort Circuit Voltage Drop Calculator
Calculate short circuit voltage drop with inputs, formulas, and instant results.
๐งฎPump Power Calculator
Calculate pump power with inputs, formulas, and instant results.
๐งฎOutdoor Lighting Calculator
Calculate low-voltage outdoor lighting transformer size from total fixture wattage.
๐งฎAcibeam Capacity Flexure Calculator
Calculate acibeam capacity flexure with inputs, formulas, and instant results.
๐งฎAcicolumn Capacity Calculator
Calculate acicolumn capacity with inputs, formulas, and instant results.
๐งฎSoil Bearing Capacity Calculator
Calculate soil bearing capacity with inputs, formulas, and instant results.